LC Uniboot 90 Degree Bent
LC Uniboot 90 Degree Bent design allows one cable to carry both fibers, reducing cable congestion when routing, and is suitable to be used in high-density fiber patching in data centers which need space saving and reduce cable management troubles like Data Centers,Local Area Networks,High-Density Applications,Interconnects,oss-connects . Reverse-polarity design allows for quick and easy polarity conversion without exposing the fibers or needing any tools.
LC Uniboot 90 Degree Bent
LC Uniboot 90 Degree Bent design allows one cable to carry both fibers, reducing cable congestion when routing, and is suitable to be used in high-density fiber patching in data centers which need space saving and reduce cable management troubles like Data Centers,Local Area Networks,High-Density Applications,Interconnects,oss-connects . Reverse-polarity design allows for quick and easy polarity conversion without exposing the fibers or needing any tools.

LC Uniboot 90 Degree Bent
Application
- Data Centers
- Local Area Networks
- High-Density Applications
- Interconnects
- oss-connects
specification
- Uniboot with a Single Housing
- Low insertion loss and added loss.
- Height of attenuation
- High back loss, small volume, light
- End-face geometry and quality superior than IEC and Telcordia standards
- LSZH, OFNP, OFNR cable
- Mechanical performance: IEC 61754-20 standard.
- RoHS and REACH materials compliant.
Connector Types
Type | Reference | Note | |
LC |
IEC 61754-20 |
Single mode | UPC: Blue connectors , White boots |
Multimode | UPC: Grey or Aqua Connectors , White boots |
Dimensional Diagrams
1.LC Uniboot (90 Degree Bent) 3.0mm patchcord

LC Uniboot 90 Degree Bent
Patch cord versions
Jumper tolerance requirement | |
Overall length (L) (M) | length of tolerance(CM) |
0<L≤20 | +10/-0 |
20<L≤40 | +15/-0 |
L>40 | +0.5%L/-0 |
Cable Structure

LC Uniboot 90 Degree Bent
Cable Parameters
Fiber account |
OD(mm) |
Nominal Weight (kg/km) |
Max.tensile Strength(N) |
Max.Crush Resistance (N/100mm) |
Min.Bending Radius(mm) |
|||
Short-term | Long-term | Short-term | Long-term | Dynamic | Static | |||
2 | 3.0±0.15 | 7.5 | 150 | 80 | 500 | 150 | 20D | 10D |
Optical Characteristics
Item |
Parameter |
Reference |
|
Single mode | Multimode | ||
Insertion loss | Typical value≤0.15dB ; Maximum≤0.30 | Typical value≤0.15dB ; Maximum≤0.30 | IEC 61300-3-34 |
Return loss | ≥ 50dB (UPC) | ≥30dB (UPC) | IEC 61300-3-6 |
End-Face Geometry
Item | UPC (Ref: IEC 61755-3-1) | APC (Ref: IEC 61755-3-2) |
Radius of curvature (mm) | 7 to 25 | 5 to 12 |
Fiber height (nm) | -100 to 100 | -100 to 100 |
Apex offset (μm) | 0 to 50 | 0 to 50 |
APC angle (°) | / | 8° ±0.2° |
Key error (°) | / | 0.2° max |
End-Face Qualty (SM)
Zone | Range (μm) | Scratches | Defects | Reference |
A: Core | 0 to 25 | None | None |
IEC 61300-3-35:2015 |
B: Cladding | 25 to 115 | None | None | |
C: Adhesive | 115 to 135 | None | None | |
D: Contact | 135 to 250 | None | None | |
E: Rest of ferrule | None | None |
End-Face Qualty (MM)
Zone | Range (μm) | Scratches | Defects | Reference |
A: Core | 0 to 65 | None | None |
IEC 61300-3-35:2015 |
B: Cladding | 65 to 115 | None | None | |
C: Adhesive | 115 to 135 | None | None | |
D: Contact | 135 to 250 | None | None | |
E: Rest of ferrule | None | None |
Mechanical Characteristics
Test | Conditions | Reference |
Endurance | 500 matings | IEC 61300-2-2 |
Vibration | Frequency: 10 to 55Hz, Amplitude: 0.75mm | IEC 61300-2-1 |
Cable retention | 100N (patch cable); 5N (pigtail) | IEC 61300-2-4 |
Strength of coupling mechanism | 80N for 2 to 3mm cable | IEC 61300-2-6 |
Cable torsion | 15N for 2 to 3mm cable | IEC 61300-2-5 |
Fall | 10 drops, 1m drop height | IEC 61300-2-12 |
Static lateral load | 1N for 1h (patch cable); 0.2N for 5min (pigtail) | IEC 61300-2-42 |
Cold | -25°C, 96h duration | IEC 61300-2-17 |
Dry heat | +70°C, 96h duration | IEC 61300-2-18 |
Change of temperature | -25°C to +70°C, 12 cycles | IEC 61300-2-22 |
Humidity | +40°C at 93%, 96h duration | IEC 61300-2-19 |